110 Part Number 80-1505-3 6/11
CVD1486 WATER COOLED CONDENSING UNIT
Place the ice machine toggle switch into the OFF
position.
1. "Front seat" (shut off) the receiver service valve.
Hang a tag on the switch as a reminder to open
the valve before restarting.
2. Perform steps 1-6 on previous page.
3. Insert a large screwdriver between the bottom
spring coils of the water regulating valve. Pry
upward to open the valve.
4. Hold the valve open and blow compressed air
through the condenser until no water remains.