28 Part Number 80-1505-3 6/11
CONDENSING UNIT CLEARANCE
REQUIREMENTS
CVD675/CVD685/CVD885/CVD1075/CVD1085/
CVD1185/
CVD2075/CVD2085
Top/Sides - There is no minimum clearance required,
although 6” (15.2 cm) is recommended for efficient
operation and servicing only.
Front/Back - 48” (122 cm)
CVD1285/CVD1485/CVD1885
Top/Sides - There is no minimum clearance required,
although 6” (15.2 cm) is recommended for efficient
operation and servicing only.
Front - 24” (61 cm)
Back - 48” (122 cm)
CVD1486 ONLY
Top - 5” (12.7 cm) is required for efficient operation
and servicing.
Front/Back/Sides - 12” (30.5 cm)
CVD3085
Top/Sides - There is no minimum clearance required,
although 8” (20.3 cm) is recommended for efficient
operation and servicing only.
Front/Back - 24” (122 cm)
NOTE: 24” (61.0 cm) on all sides is recommended
to allow easy access.