Part Number 80-1505-3 6/11 127
SAFETY LIMIT #2
Single & Twin Models
- Harvest time exceeds 3.5
minutes for 500 consecutive harvest cycles
Quad Models
- Harvest time exceeds 7 minutes for
500 consecutive harvest cycles
Possible Cause Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
page 151
Water System
Water area (evaporator) dirty
Dirty/defective water dump valve
Vent tube not installed on water outlet drain
Water freezing behind evaporator
Plastic extrusions and gaskets not securely
mounted to the evaporator
Low water pressure (20 psig min.)
Loss of water from sump area
Clogged water distribution tube
Dirty/defective water fill valve
Defective water pump
Electrical System
Ice thickness probe out of adjustment
Ice thickness probe dirty
Bin switch closed/defective
Premature harvest
Refrigeration System
Non-Manitowoc components
Improper refrigerant charge
Defective head pressure control valve
Defective harvest valve
TXV flooding (check bulb mounting)
Defective fan cycling control
CVD1486 Only - Water inlet valve is incorrectly
adjusted or will not close during harvest cycle.