3.6 SERVICE DISCONNECT ATS CONFIGURATION
If the transfer switch is ordered with Service Entrance rating type and is to be used as
Service Equipment, following the procedure described below:
WARNING: The transfer switch must be de-energized prior to opening the enclosure
to access Neutral Bonding strap. Failure to follow these instructions can result in
death or serious injury.
1. Connect the Bonding Strap
to Neutral
2. Apply the Service Disconnect
label supplied with the ATS to the
front of the door under the circuit
breaker toggle