TS 910 TRANSFER SWITCH
PM140 REV 2 14/01/23 1 Thomson Power Systems
1 PRODUCT REVISION HISTORY
The following information provides an historical summary of changes made to this product since the
original release.
Owners Manual Version
Rev 0 12/02/09
Original release
Rev 1 12/08/28
Added 3 Phase Product Information
Contact Thomson Power Systems, to obtain applicable instruction manuals or if in doubt
about any matter relating to installation, operation or maintenance. Soft copy of the most
current version is available at
www.thomsontechnology.com.
NOTE: All information contained in this manual is for reference only and is subject
to change without notice.
2 EQUIPMENT STORAGE
The following procedures are required for correct storage of the transfer switch prior to installation.
CAUTION!!!
Failure to store equipment under the specified environmental conditions may cause
equipment damage and void warranty.
The transfer switch shall be stored in an environment with a temperature range not exceeding -4° to
+158° Fahrenheit (-20° to +70° Celsius) and a humidity range not exceeding 5%-95% non-
condensing. Before storing, unpack sufficiently to check for concealed damage. If concealed
damage is found, notify the ATS supplier and the Carrier immediately. Repack the transfer switch
with the original packing material (or equivalent). Protect from physical damage. Do not stack. Store
indoors in a clean, dry, well ventilated area free of corrosive agents including fumes, salt and
concrete/cement dust. Apply heat as necessary to prevent condensation.