17.3 200A, 2P TRANSFER SWITCH UPSTREAM CIRCUIT PROTECTIVE DEVICES
200A, 2 Pole transfer switches are suitable for use on circuits capable of delivering 10,000
Amps (RMS symmetrical), 240V when protected by the following upstream circuit breakers:
EATON/
CUTLER
CSR, BWH, FD, HFD, JDB, JD, HJD, JDC, DK, KD,
KDB, HKD, KDC, LCL, LA
Q2, QOM2, QOM2-VH, Q2H, KI, KA, KH, KC, QB,
QD, QG, QJ, LE, LX, LXI, LC, LI, LA, LH
FD6-A, FXD6-A, HFD6, CFD6
17.4 200A, 3P TRANSFER SWITCH UPSTREAM CIRCUIT PROTECTIVE DEVICES
200A, 3 Pole transfer switches are suitable for use on circuits capable of delivering 25,000
Amps (RMS symmetrical), 240V when protected by the following upstream circuit breakers:
EATON/
CUTLER
HAMMER
ED, EDC, EDH, EDS, FD, FDC, FDCE, FDE, HCA,
HFD, HFDE, HJD, JD, JDB, JDC, JGC, JGE, JGH,
JGS, JGU, JGX, CHKD, CKD, DK, HKD, KD, KDB,
JD, JG, JJ, JL, KA, KC, KH, KI, QD, QG, QJ, LA, LC,
LE, LH, LX, LXI, Q4
HQJ2, HQJ2-H, QJ2H, CFD6, FD6A, FXD6A, HFD6,
HFG, HFXD6, HHFD6, HHFXD6, LFG, NFG, CJD6,
HHJD6, HHJXD6, HJD6, HJXD6, HJG, JXD2, JD6,
Note: 200A Service Entrance Rated TS 910 Transfer switches have an Interrupting Rating