TS 910 TRANSFER SWITCH
PM140 REV 2 14/01/23 28 Thomson Power Systems
17.5 400A, 2P TRANSFER SWITCH UPSTREAM CIRCUIT PROTECTIVE DEVICES
200A, 3 Pole transfer switches are suitable for use on circuits capable of delivering 25,000
Amps (RMS symmetrical), 240V when protected by the following upstream circuit breakers:
EATON/
CUTLER
DK, KDB, KD, CKD, HKD, CHKD, KDC, LCL, LA
TRIPAC
LA, LH, LC, LI, LE, LX, LXI,
SIEMENS NJGA, HJGA, LJGA, JXD2, JD6, JXD6, HJD6,
HJXD6, HHJD6, HHJXD6, CJD6, SJD6, SHJD6,
17.6 400A, 3P TRANSFER SWITCH UPSTREAM CIRCUIT PROTECTIVE DEVICES
200A, 3 Pole transfer switches are suitable for use on circuits capable of delivering 50,000
Amps (RMS symmetrical), 240V when protected by the following upstream circuit breakers:
CUTLER
DK, KDB, KD, CKD, HKD, CHKD, KDC, LCL, LA
TRIPAC
LA, LH, LC, LI, LE, LX, LXI,
SIEMENS NJGA, HJGA, LJGA, JXD2, JD6, JXD6, HJD6,
HJXD6, HHJD6, HHJXD6, CJD6, SJD6, SHJD6,
Note: 400A Service Entrance Rated TS 910 Transfer switches have an Interrupting Rating
on the Utility supply of 25,000 Amps (RMS symmetrical).