TS 910 TRANSFER SWITCH
PM140 REV 2 14/01/23 53 Thomson Power Systems
Generator does not start up or stop
when it should
Verify remote engine control panel is set for automatic mode
Verify engine start wiring is on correct terminals of TSC 9
controller.
Verify engine start wiring is not loose at transfer switch and/or
at the engine control panel.
Verify time delay setting of the TSC 9 controller
Exercise test has been incorrectly cancelled before Genset has
operated on load for 60 seconds minimum (refer to manual
section 18.9.2). Exercise Alarm condition has been activated (
Must (Flashing Alarm LED light and Exercise Light Flashing
Fast). Must reset alarm- Press and hold the “E” and “T”
pushbutton together for 10 seconds until alarm LED goes out.
No time delay when there should be
Generator Exerciser not operating
correctly