Model: LC5296 Dual Channel Temperature Controller
Doc. Ref. no.:- m61C/om/101
Issue no. 01D/ENGG-114
User’s Manual Page 19 of 30
RT-1
(rt-1)
Retransmission
1 Type
Retransmission-1 Output Type
This output is according to PV input.
Zero & Span acts as Min & Max value of
retransmission o/p scale respectively.
0-5v / 1-5v / 0-10 / 4-20 / 0-20
0 : 0-5V
1 : 1-5V
2 : 0-10V
3 : 4-20mA
4 : 0-20mA
Voltage or Current is Jumper Selectable from
the Hardware.
0
(0-5V)
RT-2
(rt-2)
Retransmission
2 Type
Retransmission-2 Output Type
This output is according to PV input.
Zero & Span acts as Min & Max value of
retransmission o/p scale respectively.
0-5v / 1-5v / 0-10 / 4-20 / 0-20
0 : 0-5V
1 : 1-5V
2 : 0-10V
3 : 4-20mA
4 : 0-20mA
Voltage or Current is Jumper Selectable from
the Hardware.
0
(0-5V)
if Device
supports Dual
Retransmission
Output
HY-1
(Hy-1)
Hysteresis 1
(For Relay-1)
Hysteresis Value (in °C) for Relay-1 during
ON-OFF type Control.
1 to 100
RTD Input
0.1 to 10.0
RTD.1 Input
1 to 100
Linear Input with DP=0
0.1 to 10.0
Linear Input with DP=1
0.01 to 1.00
Linear Input with DP=2
0.001 to
0.100
Linear Input with DP=3
5