f. If pressures do not react as described, check un
loader coil or repair unloader mechanism as re
quired.
g. When testing is com p lete, reconnect transducer
and unloader connectors and remove manifold
gauge set.
h. Disconnection of the suction pressure transducer
will cause an alarm. Once th e transducer is reco n
nected, the alarm will go to inactive and can then
be cleared.