Starting and stopping
from an external device
(
or
)
(
or
)
1]
2]
Start/stop connector
Discharging can be started and stopped from external
equipment via the connector named START/STOP.
Male connector for this terminal is "Neutrik NC3MX".
The start/stop circuits are galvanically isolated from
other circuits in TORKEL.
Two or more TORKEL units can be started simultane-
ously since the START/STOP connectors can be con-
nected in parallel and triggered by a single contact.
Starting
Connect a dry contact to pin 2 and pin 3 in the
connector.
Closing and then opening the contact will cause
TORKEL to start the discharge.
5 V is supplied for the dry contact and the current
is limited internally to about 5 mA.
Stopping
Connect a dry contact to pin 1 and pin 3 in the
connector.
Closing and then opening the contact will cause
TORKEL to stop the discharge.
5 V is supplied for the dry contact and the current
is limited internally to about 5 mA.