3 8
T O R K E L 8 2 0 / 8 4 0 / 8 6 0
P r o g r a m m a E l e c t r i c A B
Z P - B S 0 6 E R 1 0 1
Systems containing TORKEL 820
and TXL850
48 V battery (24 cells)
Discharge from 2.15 to 1.8 V/cell
Maximum con-
stant current (A)
Number of units
TORKEL 820
Number of units
TXL850
499 1 1
729 1 2
959 1 3
1189 1 4
1459 2 4
1688 2 5
1918 2 6
2148 2 7
2378 2 8
2608 2 9
2837 2 10
Systems containing
TORKEL 840/860 and TXL830
24 V battery (12 cells)
Discharge from 2.15 to 1.8 V/cell
Maximum con-
stant current (A)
Number of units
TORKEL 840/860
Number of units
TXL830
263 1 1
445 2 1
670 2 2
895 2 3
1005 3 3
1230 3 4
1455 3 5
Systems containing
TORKEL 840/860 and TXL850
48 V battery (24 cells)
Discharge from 2.15 to 1.8 V/cell
Maximum con-
stant current (A)
Number of units
TORKEL 840/860
Number of units
TXL850
264 1 1
449 2 1
679 2 2
909 2 3
1019 3 3
1249 3 4
1478 3 5
Systems containing
TORKEL 840/860 and TXL870
110 V battery (54 cells)
Discharge from 2.15 to 1.8 V/cell
Maximum con-
stant current (A)
Number of units TORKEL
840/860
Number of units
TXL870
188 1 1
266 1 2
344 1 3
422 1 4
532 2 4
610 2 5
688 2 6
766 2 7
845 2 8
923 2 9
1001 2 10
120 V battery (60 cells)
Discharge from 2.15 to 1.75 V/cell
Maximum con-
stant current (A)
Number of units
TORKEL 840/860
Number of units
TXL870
194 1 1
278 1 2
363 1 3
473 2 3
557 2 4
642 2 5
726 2 6
810 2 7
895 2 8
979 2 9
220 V battery (108 cells)
Discharge from 2.15 to 1.8 V/cell
Maximum con-
stant current (A)
Number of units
TORKEL 840/860
Number of units
TXL870
94 1 1
133 1 2
188 2 2
227 2 3
266 2 4
306 2 5
345 2 6
384 2 7
423 2 8
463 2 9