5 2
T O R K E L 8 2 0 / 8 4 0 / 8 6 0
P r o g r a m m a E l e c t r i c A B
Z P - B S 0 6 E R 1 0 1
48 V battery (24 cells)
3)
1.80 V / cell (43.2 V) 0 – 110 A 0 – 4.75 kW
1.75 V / cell (42.0 V) 0 – 110 A 0 – 4.62 kW
1.60 V / cell (38.4 V) 0 – 110 A 0 – 4.22 kW
110 V battery (54 cells)
3)
1.80 V / cell (97.2 V) 0 – 110 A 0 – 10.7 kW
1.75 V / cell (94.5 V) 0 – 110 A 0 – 10.4 kW
1.60 V / cell (86.4 V) 0 – 110 A 0 – 9.5 kW
120 V battery (60 cells)
3)
1.80 V / cell (108 V) 0 – 110 A 0 – 11.9 kW
1.75 V / cell (105 V) 0 – 110 A 0 – 11.5 kW
1.60 V / cell (96 V) 0 – 110 A 0 – 10.5 kW
220 V battery (108 cells)
3)
1.80 V / cell (194 V) 0 – 55 A 0 – 10.7 kW
1.75 V / cell (189 V) 0 – 55 A 0 – 10.4 kW
1.60 V / cell (173 V) 0 – 51.0 A 0 – 8.82 kW
240 V battery (120 cells)
3)
1.80 V / cell (216 V) 0 – 55 A 0 – 11.9 kW
1.75 V / cell (210 V) 0 – 55 A 0 – 11.5 kW
1.60 V / cell (192 V) 0 – 55 A 0 – 10.5 kW
UPS battery (180 cells)
3)
(TORKEL 860)
1.70 V / cell (306 V) 0 – 38 A 0 – 15 kW
1.60 V / cell (288 V) 0 – 38 A 0 – 15 kW
UPS battery (204 cells)
3)
(TORKEL 860)
1.80 V / cell (367 V) 0 – 34 A 0 – 15 kW
1.60 V / cell (326 V) 0 – 34 A 0 – 15 kW
3) 2.15 V per cell when test starts
Time (max) 24 h
Time interval 1 – 24 s
Load section
Max. battery voltage 288 V DC (TORKEL 840)
480 V DC (TORKEL 860)
Max. current 110 A
Max. power 15 kW
Load patterns Constant current, constant power,
constant resistance, current or
power profile
Current setting
0-110.0 A (2999.9 A)
1)
Power setting 0-15.00 kW (299.99 kW)
1)
Resistance setting 0.1-2999.8 Ω
Battery voltage range,
TORKEL 840
4 ranges, selected automatically at
start of test
Battery voltage range,
TORKEL 860
5 ranges, selected automatically at
start of test
Stabilization (For
internal current meas-
urement)
±(0.5% of reading +0.5 A)
Battery volt-
age
Highest permis-
sible current
Resistor ele-
ment (Nomi-
nal values)
Range 1 10 – 27.6 V 110 A 0.165 Ω
Range 2 10 – 55.2 V 110 A 0.275 Ω
Range 3 10 – 144 V 110 A 0.55 Ω
Range 4 10 – 288 V 55 A
3.3 Ω
Range
5
2)
10 – 480 V 55 A (max power
15 kW)
3.3 Ω
1) Maximum value for a system with more than one load unit
2) TORKEL 860
Inputs, maximal values
EXTERNAL CURRENT
MEASUREMENT
1 V DC, 300 V DC to ground. Cur-
rent shunt should be connected to
the negative side of the battery
START / STOP Closing / opening contact
Closing and then opening the
contact will start / stop Torkel. It is
not possible to keep the contacts in
closed position. (Min. time open is
25 ms).
Delay until start
200 – 300 ms
Stop delay 100 – 200 ms
Battery 480 V DC, 500 V DC to ground
VOLTAGE SENSE 480 V DC, 500 V DC to ground
SERIAL < 15 V
ALARM 250 V DC 0.28 A
28 V DC 8 A
250 V AC 8 A
Outputs, maximal values
START / STOP 5 V, 6 mA
TXL Relay contact
SERIAL < 15 V
ALARM Relay contact
Discharging capacity, examples
12 V battery (6 cells)
3)
Final voltage Constant cur-
rent
Constant
power
1.80 V / cell (10.8 V) 0 – 50.0 A 0 – 0.54 kW
1.75 V / cell (10.5 V) 0 – 49.0 A 0 – 0.51 kW
1.67 V / cell (10.0 V) 0 – 46.0 A 0 – 0.46 kW
24 V battery (12 cells)
3)
1.80 V / cell (21.6 V) 0 – 110 A 0 – 2.37 kW
1.75 V / cell (21.0 V) 0 – 110 A 0 – 2.31 kW
1.60 V / cell (19.2 V) 0 – 100 A 0 – 1.92 kW