Additional requirements for the servo drives concerning the UL approval Page 43
8 Additional requirements for the servo
drives concerning the UL approval
This chapter gives further information concerning the UL approval of the ARS 2102 SE, ARS 2105 SE and
ARS 2108 SE.
8.1 Circuit protection
In case of a required UL-certification the following data for the main fuse are to be
considered:
Listed Circuit Breaker according to UL 489, rated 277 Vac, 16 A, SCR 10 kA
8.2 Wiring and environment regards
Use 60/75 or 75°C copper (CU) wire only.
The terminal tightening torque is 0.22...0.25 Nm.
To be used in a Pollution Degree 2 environment only.
8.3 Motor temperature sensor
Motor overtemperature sensing is not provided by the drive according to UL.
When a UL-certification is required, then in order to prevent motor overtemperatures the servo drives may
only be operated in connection with motors that are provided with an integrated motor temperature
sensor. The sensor has to be connected to the servo drive and the temperature monitoring has to be
activated accordingly on the software side.
Mounting Instructions „Servo drives ARS 2100 SE“ Version 5.0

Other manuals for Metronix ARS 2100 SE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Metronix ARS 2100 SE Series and is the answer not in the manual?

Metronix ARS 2100 SE Series Specifications

General IconGeneral
BrandMetronix
ModelARS 2100 SE Series
CategoryServo Drives
LanguageEnglish

Related product manuals