34007117EN/AB - Page 21
3. Operation
Configurable function
Output voltage on battery power
Upper threshold for transfer to battery power
Fader-mode cut-in threshold
Booster-mode cut-in threshold
Lower threshold for transfer to battery power
Maximum input-voltage range
Default setting
230 V
294 V
265 V
184 V
160 V
Disabled
Options
200 V - 220 V - 240 V
271 to 294 V
244 to 265 V
184 to 207 V
160 to 180 V
Enabled
(1)
Configurable function
UPS sensitivity level
Default setting
Normal
Options
High or low
Voltage-thresholds tab
Sensitivity tab
For more informations about these settings, refer to the Help function of the "UPS Driver" software.
(1) Lower threshold for transfer to battery power = 150 V