ESG‐InvM
24
MideaESG‐InvMSeriesPoolHeatPumpTechnicalManual
Whentheoutdoorunitstops:TheEXVfirstmovesto480(steps)andremainsfor30seconds,thenclosesfully,thenmoves
tothestandbyposition(480(steps)).
• Four‐wayValveControl
Thefour‐wayvalveisusedtochangethedirectionofrefrigerantflowthroughthewatersideheatexchangerinorderto
switchbetweencoolingandheatingmode.
Duringheatingoperation,thefour‐wayvalveison;duringcoolinganddefrostingoperations,thefour‐wayvalveisoff.
• Fan
Thespeedoftheoutdoorunitfanisadjustedinsteps,asshownbelow
Fanspeedindex
Fanspeed(rpm)
MSC‐70D2N8‐A MSC‐90D2N8‐A MSC‐120D2N8‐A
W1 150 150 150
W2 200 200 200
W3
250 250 250
W4
300 300 300
W5
350 350 350
W6 400 400 400
W7
450 450 450
W8
530 530 530
W9
600 600 600
W10 650 650 650
W11 / 730 730
W12 / 780 780
W13 / / 850
5 SpecialControl
5.1 OilReturnOperation
Inordertopreventthecompressorfromrunningoutofoil,theoilreturnoperationisconductedtorecoveroilthathas
flowedoutofthecompressorandintotherefrigerantpiping.Whentheoilreturnoperationisbeingconducted,themain
PCBdisplayscoded0.
Theoilreturnoperationstartswhenthefollowingconditionoccurs:
• Whenthecompressorcumulativeoperatingtimewithrunningrotationspeedlessthan42rpsreaches6hours.
Theoilreturnoperationceaseswhenanyoneofthefollowingconditionsoccurs:
• Oilreturnoperationdurationreaches5minutes.
• Compressorstops.
Forheatingmode:
Component Wiringdiagramlabel Controlfunctionsandstates
Invertercompressor COMP Runsatoilreturnoperationrotationspeed
DCfanmotor FAN Controlledaccordingtoheatingmode
Electronicexpansionvalve EXV 304(steps)
Four‐wayvalve 4‐WAY On