Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
10
0.75×3-core with shielding
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-freezing protection in cooling mode.
5) Anti-freezing protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temp. difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low-temperature protection of shell and tube heat
exchanger.
Sound level(semi-anechoic )
Cooling:5~17 Heating:45~50
Cooling:10~52 Heating:-10~21
Note: Specifications are based on the following conditions:
Cooling : (*1) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C (117℉) DB.
(*2) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 46˚C(140℉) DB.
Heating : warm water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°CWB.
Water side fouling factor: 0.086m
2