MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
149
2) Current protection
3) High temperature protection of condenser
High temperature protection of
condenser.
Check the fan motor,
capacitor (1 phase) or
start up water pump.
Empty, vacuuming and
append refrigerant if
necessary.
Check power supply,
start up the unit after
normal power supply.
Inform the customer service
center.
Air is in system, filled too much
refrigerant(Generally happened
after maintenance.)
The fin of heat exchanger is
dirty or aged in cooling mode.
Replace temperature
sensor.
Check the fan motor,
capacitor (1 phase).
Replace installation
position of unit.
The installation position of unit
results in bad heat transfer of
condenser.
In cooling mode, the fan motor
stop running, reversal and run
slowly.
The temperature sensor of
condenser bring drifting when
collect temperature.
Inform the customer service
center.
The fin of heat exchanger is
dirty or aged in cooling mode,
or the shell and tube scaled
strong.
The fan motor stopped running
in cooling mode, reversal and
run slowly. The water pump
didn’t start up or less water
flow in heating.