MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
201
Press the button, inquire state information of No. 0 to No. 15 outdoor units (the default is state information of
No.0 unit) and enter inquiry state. After entering inquiry state, inquire the information of the former unit or the
following unit through “ADDRESS/+” and “ADDRESS/-”. After a certain outdoor unit is selected, state
information of the outdoor unit can be inquired through “page up” and “page down”. There are two possible
inquiry sequences.
1).Errorprotection outlet water temperature Touinlet water temperature Tinoutdoor ambient
temperatures T4outdoor pipe temperature T3Aoutdoor pipe temperature T3bcurrent of the compressor
IA current of the compressor Ibanti-freezing temperature T6electronic expansion valve opening FA
electronic expansion valve opening FbError......The wired controller only displays the last fault information
and the protection information, when query is conducted on fault and protection information.
2). outdoor pipe temperature T3AprotectionErroroutlet water temperature Toucurrent of the
compressor Ibcurrent of the compressor IA Setting temperature Tsoutdoor ambient temperatures T4
outdoor pipe temperature T3boutdoor pipe temperature T3A......The wired controller only displays the last
fault information and the protection and protection information.
CLOCK button
Press the CLOCK button once Press for the first time, and enter to the week adjustment, Press for
the second time, and enter to the hour adjustment,Press for the third time,and enter the minute adjustment.
The numerical valve of week, hour and minute can be adjusted by “ADDRESS/+” and “ADDRESS/-”, after the
adjustment then press the OK button for the setting confirmation.
TEMP SET button
Setup the total water outlet temperature in cooling and heating mode.
The numerical valve of temperature setting can be adjusted by “ADDRESS/+” and “ADDRESS/-
TIMER SET button
Press the button can enter the timer set adjustment. The numerical valve of the week, the start period, the
end period, the operation mode and the setting temperature can be adjusted by “ADDRESS/+” and
“ADDRESS/-”.
OK button
Once finished upon, press OK key, wired controller will delivery order to main unit.
CANCEL button
Press the button can return to the interface previous and not save the setting information when the timer
switch is ON.
If press the button for 3 seconds continuously, all the setting information of the timer will be cleared.
10 ADDRESS/+ button

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MGBT-F30W/RN1 and is the answer not in the manual?

Midea MGBT-F30W/RN1 Specifications

General IconGeneral
BrandMidea
ModelMGBT-F30W/RN1
CategoryChiller
LanguageEnglish

Related product manuals