R410A All DC Inverter V4+S Series 60Hz      MCAC-VTSM-2015-09 
112 Installation 
2.  Supporting, hanging  and  mounting  brackets  cannot be  installed  at  air  vent,  valves,  checking  door  and 
automatically  controlled  device,  and  distance  to  air  opening  or  plugged  tube  shall  not  be  less  than 
0.66ft.(200mm). 
3. Hanging brackets should not be hung above flanges. 
4. Thickness of flange gasket should be 0.12-0.2”(3-5mm). Gasket should set flat against flange and inserting 
to pipe is not allowed. Set up fixed points in suitable areas for hanging pipe to prevent vibration. 
5. Vertical splice seam of duct should be stagger. Make sure there is no vertical seam at the bottom of duct 
installed horizontally. As for the installation of flexible short duct, keep proper tightness and no distortion. 
6. All metal parts (including supporting, hanging and mounting brackets) in piping system should be given 
anti-corrosion treatment. 
6.4 Installation of Assembly 
1. Air flow regulators should be installed in easily accessible areas.. 
2. The air vent should be installed firmly and duct should be connected tightly. Duct construction should blend 
with building design. The appearance should be smooth and level, and regulation is flexible. 
3. If air vent is installed horizontally, level deviation should be no more than 3/1000. If air vent is installed 
vertically, deviation from perpendicular should be no more than 2/1000. 
4. Air vent in same room should be installed at the same height, and put in order. 
7.  Heat Insulation Engineering 
The insulation of refrigerating equipment and piping follows general insulation methods. Insulating shall be 
carried out in a manner best suited for selected insulation material. 
7.1 Insulation of Refrigerant Piping 
7.1.1 Operational procedure of refrigerant piping insulation 
Construction of refrigerant pipe → insulation (excluding joints) →air tightness test → joint insulation 
Joints: Insulation of welded joints or flanges should be carried out after air tightness is confirmed. 
7.1.2 Purpose of refrigerant piping insulation 
1. During operation, temperature of gas pipe and liquid pipe will be heated or cooled excessively. Therefore, is 
necessary to insulate in order to guarantee unit performance and compressor life span. 
2. Gas pipe temperature is very low during cooling. If insulation is insufficient, condensation will form and 
cause leakage. 
3. Temperature of gas pipe is very high (generally 122-212°F(50-100°C) during heating. Insulation serves as a 
necessary protection from burning.. 
7.1.3 Selection of insulation materials for refrigerant piping 
Adopt closed-cell foam insulation materials with a B1 fire resistant rating and over 248°F(120°C) of constant 
burning performance. 
7.1.4 Thickness of insulation layer 
1. When outer diameter of copper pipe (d) is less than or equal to 1/2”(12.7mm), the thickness of insulation 
layer (δ) shall be above 19/32”(15mm). 
When outer diameter of copper pipe (d) is more than or equal to 5/8”(15.88mm), the thickness of insulation 
layer (δ) shall be above 25/32“(20mm). 
2. In hot and wet environments, the above recommended value shall be doubled. 
Note: The outdoor piping shall be protected by metal casing to protect against sunlight, rain, air erosion and 
any other potential causes of damage. 
7.1.5 Installation and main points of insulation construction 
1.  Example  of  incorrect  insulation:  Gas  and  liquid  piping  are  insulated  together  reducing  air  conditioner 
efficiency and effectiveness. 
2. Example of correct installation: