MCAC-VTSM-2015-09      R410A All DC Inverter V4+S Series 60Hz 
Troubleshooting 141 
4.11   H7: Faulty indoor unit quantity 
The error will only display on the master unit, all the ODUs will be on standby. It will display when the quantity 
of indoor units decrease above 3 minutes. 
 
 
 
Note:   
* How to check for IDU transformer 
The voltage input of IDU transformer is 220V, the voltage output is AC9V (yellow-yellow) and AC13.5V (brown-brown). 
* How to check for 485 communication IC 
The normal voltage between “P” and “GND” is DC2.5~2.7V, between “Q” and “GND” is DC2.5~2.7V. If the voltage is out of the 
normal range, the 485 communication IC is disabled. 
 
* Indoor units should have unified power supply, which can protect the compressor from liquid hammering caused by dropped 
indoor units with unclosed EXV. 
   
H7: Faulty indoor unit quantity 
Communication terminals P Q E are 
loose 
Fasten the communication 
terminals 
Transformer of IDU is disabled
*
 
IDU are not unified power supply* 
Insure all the IDU have unified 
power supply 
485 communication IC is disabled
*
 
Some IDU are assigned the same 
address 
Set the IDU addresses differently