R410A All DC Inverter V4+S Series 60Hz    MCAC-VTSM-2015-09 
140 Troubleshooting 
4.9    H2: Outdoor unit quantity is decreased 
4.10   H3: Outdoor unit quantity is increased 
The error will only display on master unit, all the ODUs will be on standby. 
 
 
 
Note: All the outdoor units should have unified power supply. If the outdoor units do not unified power supply, 
units may be powered off individually leading imbalances in the system and damage. 
   
Communication wire between 
outdoor units is loose 
Fasten the communication 
wire 
Some outdoor units’ addresses 
(ENC1) are setting repeatedly 
Set the addresses (ENC1) 
differently 
Some outdoor units in combination 
are powered off (check the LED1 on 
main PCB, if LED1 is on, the main 
PCB is powered on, if LED1 is off, 
the main PCB is powered off) 
Turn on all the outdoor units 
Outdoor main PCB is damaged 
Replace the outdoor main PCB