R410A All DC Inverter V4+S Series 60Hz      MCAC-VTSM-2015-09 
16                                                                                                                                                                                          Selection Procedure 
Then calculate the outdoor capacity in 92% combination index: 26.8+{(28.3-26.8)/10}×2=27.1kW(92470Btu/h);   
  Capacity modification coefficient with pipe length 50m(164ft) and height difference 30m(98.4ft): 0.958 
  Each indoor unit cooling capacity   
Room A: MDV-D22T2 (27.1×22/258×0.958=2.21kW) (92470×7510/88000×0.958=7540Btu/h) 
Room B: MDV-D28T2 (27.1×28/258×0.958=2.82kW) (92470×9550/88000×0.958=9620Btu/h) 
Room C: MDV-D36T2 (27.1×36/258×0.958=3.62kW) (92470×12300/88000×0.958=12350Btu/h) 
Room D: MDV-D45T2 (27.1×45/258×0.958=4.53kW) (92470×15400/88000×0.958 =15460Btu/h) 
Room E: MDV-D56T2 (27.1×56/258×0.958=5.64kW) (92470×19110/88000×0.958=19250Btu/h) 
Room F: MDV-D71T2 (27.1×71/258×0.958=7.14kW) (92470×24200/88000×0.958=24360Btu/h) 
2.4 Conclusion 
Generally, this result is acceptable, therefore the calculation process has been completed. But if it appears that 
the result is not acceptable, the above process may be repeated. 
Remark: In this sample, other capacity modification indexes were not considered and are assumed as 1.0. 
For more details about the effect factor such as outside ambient/inside ambient DB/WD, please refer to the 
performance table of indoor and outdoor units.