R410A All DC Inverter V4+S Series 60Hz      MCAC-VTSM-2015-09 
34 Specifications & Performances 
  When the outdoor unit is lower than the surrounding obstacle, to avoid cross connection of the outdoor hot 
air from affecting the heat exchange capabilities, please add an air director onto the exhaust hood of the 
outdoor unit to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely 
H-h). Please make the air director on site. 
   
  If miscellaneous articles are piled around the outdoor unit, such articles must be 800mm (31-1/2in) below 
the  top  of  the  outdoor  unit.  The  articles  must  be  800mm  (31-1/2in)  below  the  top  of  the  outdoor  unit. 
Otherwise, a mechanical exhaust device must be added. 
   
Unit: mm (in.) 
 
   
>1000(39-3/8)
>1000(39-3/8)
>1000(39-3/8)
>100(4)
Front
Front
h
h-H
H
A
B
C
D
>45°
>1000(39-3/8)
>300(11-7/8)
Airflow deflector
Front view
B
A
Side view
C
D
B
A
Front view
B
A
Front view