2.2 Components 
 Layout 2.2.1
Figure 5-2.2: Outdoor unit main PCB components 
 
 
 
 Function of buttons SW1 to SW4 2.2.2
Table 5-2.2: Function of buttons SW1 to SW4 
 
 SW2 system check button 2.2.3
Before pressing SW2, allow the system to operate steadily for more than an hour. On pressing SW2, the parameters listed 
in Table 5-2.3 will be displayed in sequence. 
Table 5-2.3: SW2 system check 
Parameters displayed on DSP2 
Master unit: 0; slave units: 1, 2, 3 
Displayed on master unit PCB only 
Outdoor unit output metric (total of all units) 
Displayed on master unit PCB only 
Indoor unit demand metric in cooling mode 
Indoor unit demand metric in heating mode 
Indoor unit demand metric in cooling mode after ambient temperature 
correction 
Indoor unit demand metric in heating mode after ambient temperature 
correction 
Table continued on next page …     
ENC1
ENC3
S12
S3
S7
S1
ENC2
S4
S2
ENC4