V4+R VRF 50/60Hz       
70    201608 
Midea V4+R Series Service Manual 
 Procedure 4.11.4
 
Number of indoor units set on main PCB 
not same as actual number of indoor 
units
1
 
Change the setting on the PCB to be the 
same as the actual number of indoor 
units 
Some indoor units are powered off 
Power on all indoor units 
After re-starting the ODUs and IDUs and 
then waiting 2 minutes, an IDU displays 
an E1 or FE error
2
 
Refer to indoor unit troubleshooting 
guide. Resolving the indoor unit error 
resolves the outdoor unit error 
Two or more indoor units are assigned 
the same address
3
 
Setting the indoor units’ addresses 
uniquely resolves the error 
 
Notes:   
1.  The number of indoor units can be set on switches EN3 and S12 on the main PCB. Refer to Part 4, 1.1 “PCB Switches and Switch Settings”. 
2.  Indoor unit error code E1 indicates a communication error between indoor and master unit. Indoor unit error code FE indicates that an indoor unit has not 
been assigned an address. 
3.  Indoor unit addresses can be checked and manually assigned using indoor unit remote/wired controllers.