Midea V4+R Series Service Manual 
 Procedure 4.5.4
 
Temperature sensor connection on main 
PCB is loose
1
 
Ensure the sensor is connected properly 
Temperature sensor has short-circuited 
or failed
2
 
 
Notes:   
1.  Outdoor  ambient  temperature  sensor  connection  is  port  CN1  on  the  main  PCB  (labeled  32  in  Figure  5-2.1  in  Part  5,  2.2  “Ports”).  Compressor  top 
temperature sensor and discharge pipe temperature sensor connections are ports CN10 and CN11 on the main PCB (labeled 1 and 2, respectively, in Figure 
5-2.1 in Part 5, 2.2 “Ports”). 
2.  Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short-circuited.  If  the  resistance  is  not  consistent  with  the  sensor’s  resistance 
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 5-5.1 or 5-5.2 in Part 5, 5.1 “Temperature 
Sensor Resistance Characteristics”.