Part 5 - Diagnosis and Troubleshooting 
4.17 xP3 Troubleshooting 
 Digital display output 4.17.1
       
'x'  is  a  placeholder  for  the  compressor  system  (compressor  and  related  electrical  components),  with  1  representing 
compressor system A and 2 representing compressor system B. 
 
 Description 4.17.2
  1P3 indicates current protection on compressor A. 
  2P3 indicates current protection on compressor B. 
  When  the  compressor  current rises  above  the  protection value  (E655DHD-65: 21A; E405DHD-36:  12A),  the  system 
displays P3 protection and all units stop running. When the current returns to the normal range, P3 is removed and 
normal operation resumes. 
  Error code is only displayed on the unit with the error. 
 
 Possible causes 4.17.3
  Outdoor unit stop valves are closed. 
  Indoor load too large. 
  Power supply abnormal. 
  Sudden interruption of power to IDUs. 
  Excess refrigerant. 
  System contains air or nitrogen. 
  Poor condenser heat exchange. 
  High pressure side blockage. 
  Inverter module damaged. 
  Compressor damaged. 
  Main PCB damaged. 
 
 
 Procedure 4.17.4
 
ODU stop valves are closed 
The indoor load is too large
1
 
Make sure the combination ratio is less 
than 130% 
The power supply is abnormal 
Check the power supply equipment 
Sudden interruption of power to IDUs 
Inspect the system and fix the error 
Flowchart  continued  on  next  page  …