V4+R VRF 50/60Hz       
52    201608 
Midea V4+R Series Service Manual 
 Procedure 4.2.4
 
ODU addresses on switch ENC1 are set 
incorrectly
1
   
Set the ODU addresses correctly 
Communication wires between ODUs are 
not connected properly
2
 
Ensure the communication wires are 
three-core shielded cable and are 
connected properly 
Wires between outdoor main PCB and 
electric control box communication 
terminals block are loose
3
 
Ensure the wires are connected properly 
Replacing outdoor main PCB resolves the 
error 
Replace electric control box 
communication terminals block 
 
Notes:   
1.  The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system. 
Refer to Part 4, 1.1 “PCB Switches and Switch Settings”. 
2.  All the wires for H1, H2, E connections should be three-core shielded cable, the wiring should be connected according to polarity (H1 to H1, etc), the wiring 
should not be open or short circuited. Refer to the V4+R Engineering Data Book, Part 2, 5 “Wiring Diagrams” and Part 3, 9.3 “Communication Wiring”. 
3.  Refer to the V4+R Engineering Data Book, Part 2, 5 “Wiring Diagrams”.