V4+R VRF 50/60Hz 
201608    87 
Part 5 - Diagnosis and Troubleshooting 
 First troubleshooting step 4.19.5
To troubleshoot xH4 errors, first ensure that the DC bus wire is connected correctly. The DC bus wire should run from the N 
terminal  on  the  inverter  module,  through  the  current  sensor  (in  the  direction  indicated  by  the  arrow  on  the  current 
sensor), and end at the N terminal on the DC filter board.   
Figure 5-4.5: DC detection wire connection method 
 
 
 xL0 troubleshooting 4.19.6
Step 1: Check compressor 
  Check that compressor wiring is all connected properly. 
  The normal resistances of the inverter compressor are 0.9-5Ω among U V W and infinite between each of U V W and 
ground. If any of the resistances differ from these specifications, the compressor has malfunctioned. 
 
Figure  5-4.6:  Measuring  resistances  among  compressor 
terminals 
Figure  5-4.7:  Measuring  resistances between  compressor terminals 
and ground 
  If the resistances are normal, go to Step 2. 
 
Step 2: Check inverter module 
  The  DC  voltage  between  terminals  P  and  N  should  be  1.41  times  the  local  power  supply  voltage.  The  DC  voltage 
between terminals 1 and 2 should be 510-580V. If either voltage is not in the normal range, troubleshoot as for xL1 or 
xL2 errors. Refer to Part 5, 4.19.7 “xL1/xL4 troubleshooting” or Part 5, 4.19.8 “xL2 troubleshooting”. 
  Disconnect the terminals 3, 4, 5 from the inverter compressor. Measure the resistance among terminals 1, 2, 3, 4, 5. 
All the resistances should be infinite. If any of them are not infinite, the inverter module is damaged and should be 
replaced.