V4+R VRF 50/60Hz       
86    201608 
Midea V4+R Series Service Manual 
Table 5-4.1: Specific error codes for error xH4 
Inverter module protection 
DC bus low voltage protection 
DC bus high voltage protection 
Compressor frequency variation greater than 15Hz within one second protection 
Actual compressor frequency differs from target frequency by more than 15Hz protection 
Notes: 
1.  'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and 
2 representing compressor system B. 
 
The specific error codes xL0, xL1, xL2 and xL4 can also be obtained from the inverter module LED indicators. If an inverter 
module error has occurred, LED5/7 is continuously on and LED4/6 flashes. Refer to Figure 5-4.4. 
 
Figure 5-4.4: LED indicators LED4 to LED7 on main PCB