press
"ENTER"
Zero Calibration
With the material flow stopped and Test Weight removed,
press
"ZERO"
[oo 0]
displayed
press
"ENTER"
, all 4 display mode LED’s will be illuminated,
[oo ####]
displayed momentarily then,
[od 0.000]
displayed, Zero Deviation
press
"ENTER"
[oC ####]
displayed, Initial Zero Reference Count
Span Calibration
Apply the Test Weight as described in the associated flowmeter instruction manual.
press
"SPAN"
[SP 0]
displayed
press
"ENTER"
, all 4 display mode LED’s will be illuminated and
[SP ####]
displayed momentarily then,
[Sd 0.0000]
displayed, Span Deviation
press
"ENTER"
[SC ####]
displayed, Initial Span Reference Count
Remove the test weight.
BASIC CALIBRATION COMPLETE
PRESS
"RUN"
TO ENTER THE RUN MODE FOR NORMAL OPERATION
Automatic Parameter Access (APA) programming complete. Further programming, if desired, to enhance the
performance of the Compu-M requires parameter programming outside of the APA loop. These parameters
must be directly accessed.
ie.
Press
"PAR"
, press
"#",
press
"ENTER"
, key in new value, press
"ENTER".
PL-516 48