9 = custom tank design *
( refer to Applications \ Volume Application )
*
This option is divided into two levels of subparameters:
H - # where: H = level coordinate
F - # F = volume coordinate
# = breakpoint 1 to 11
Access is made by scrolling through the levels.
press display will show
Setting of the subparameters is done in the same way
as with the ‘P’ parameters.
To exit the " H " and " F " subparameters:
If P-34 0, reading will be in percent of full volume. For
volumetric reading, set conversion factoring by using P-37.
P-35 tank dimension ‘A’
the height of the bottom section of tank shapes 2, 3, 4, 5 or
the length of one end section in tank shape 7.
( not required for other tank shapes )
enter " dimension A ", in units selected per P-1 ( F = 0000 )
9
select any ‘H’ or ‘F’ parameter
return to ‘P’ parameters
ENTER
CLR
ALT
DISP
PL-443 7 – 8