P-36 tank dimension ‘L’
horizontal length of tank shape excluding parabolic ends
( not required for other tank shapes ).
enter " dimension L ", in units selected per P-1 ( F = 0.0 0 0 )
P-37 convert display
parameter value is the factor by which the measurement is to be
multiplied by before being displayed. Range is 0.001 to 9999.
enter desired factor ( F = 1 )
P-38 display offset
this value is added to material space, volume or ullage measurement
before being displayed ( P-39, P-76 or " * " key ). The mA output and
alarms are not affected by the offset. The display offset is entered in
the units programmed, subject to P-1, P-34 and P-37.
enter offset required ( F = 0.000 )
P-39 display reading options
enter : 0 = hold last alternate reading selected ( F )
1 = high total: 4 highest digits of the 8 digit totalizer
( pumped volume and OCM only )
= point 1: DLD level / transducer #1
2 = low total: 4 lowest digits of the 8 digit totalizer
( pumped volume and OCM only )
= point 2: DLD level / transducer #2
3 = head ( OCM only )
4 = flow rate ( OCM only )
5 = reading level, space, differential, volume or ullage
In the run mode, the programmer keys illustrated can be pressed
to view alternate readings. The display will return to the reading
option selected ( except option 0 ) after momentarily displaying
alternate reading.
2
3
4
0
1
PL-443 7 – 9