A
Anne OwenJul 30, 2025
What to do if Mircom FA-300 shows Battery Trouble?
- JJames HowellJul 30, 2025
If your Mircom Control Panel indicates a Battery Trouble due to low voltage (below 20.4 V), replace the batteries as soon as possible.
What to do if Mircom FA-300 shows Battery Trouble?
If your Mircom Control Panel indicates a Battery Trouble due to low voltage (below 20.4 V), replace the batteries as soon as possible.
How to fix Common Trouble on Mircom FA-300 Control Panel?
To address a Common Trouble issue on your Mircom Control Panel, check for the following potential faults: missing interconnection wiring, any missing module that was part of the configuration, or improperly secured cabling.
What to do if Mircom FA-300 Control Panel shows Ground Fault?
If your Mircom Control Panel displays a Ground Fault, check for any external wiring that might be touching the chassis or any other earth ground connection.
How to troubleshoot Circuit Trouble in Mircom FA-300 Control Panel?
To troubleshoot a Circuit Trouble in your Mircom Control Panel, check for open wiring on the affected circuit. Also, verify that the circuit is not disconnected or bypassed.
What to do if Mircom Control Panel shows Remote Fail?
If the Mircom Control Panel displays a 'Remote Fail' error, it indicates a problem with a remote annunciator or another remote device. You should check for any failures reported by these devices or a failure to communicate with them.
How to fix Circuit Trouble on Mircom FA-300 Control Panel?
If your Mircom Control Panel indicates a 'Circuit Trouble', it means there may be an issue with a particular circuit loop. You should: * Check for open wiring on the circuit loop displayed on the LCD. * Ensure the circuit hasn't been disconnected or bypassed, as this will cause a system trouble.
Brand | Mircom |
---|---|
Model | FA-300 Series |
Category | Control Panel |
Language | English |