11 DATA LOGGING FUNCTION
11.2 Data Collection Conditions
173
11
11.2 Data Collection Conditions
This section describes the timing when data is collected and the conditions under which data is collected.
Each scan
Data are collected during the END processing of each scan.
Time specification
Specify the collection time interval. Specify the timing of data collection using advanced settings as well.
Data collection at specified time interval
Data are collected at specified time interval.
Ex.
10 milliseconds (10ms)
Data collection conditions Description
Each scan Collects data during the END processing of each scan.
Time
specification
Data collection at specified time interval Collects data at specified time interval.
Data collection during the END processing after
specified time interval
Collects data during the END processing after specified time interval.
Interrupt occurrence Collects data at specified time interval after the execution of an interrupt
program.
Condition
specification
Device/label specification Collects data when the monitored data meets the specified condition during the
END processing.
Step No. specification Collects data when the specified condition is met immediately before the
execution of the specified step.
0END0END0END0END0ENDProgram
Scan time Scan time Scan time Scan time Scan time
END processing END processing END processing END processing END processing
Sampling Sampling Sampling Sampling Sampling
10ms
10ms 10ms
Set time
Sampling Sampling