358
21 DEVICES
21.9 File Register (R/ZR)
Setting file registers
This section describes the settings required to use the file registers.
Configuration procedure
This section describes the procedure to use the file registers.
1. Set the file register usage with [CPU Parameter].
2. To use the file register for each program, previously create the device memory which will become the file register file.
( GX Works3 Operating Manual)
3. When using the file registers, which are common for all programs, a file register file with the name and capacity set in the
file register setting is created.
*1
*1 If the capacity is not set, it must be set when creating a file register file and writing it to the programmable controller in the same manner
as the procedure 2.
4. Write parameters and file register files into the CPU module.
File register setting
This setting must be completed before using the file registers.
[CPU Parameter] [File Setting] [File Register Setting]
Window
Displayed items
Precautions
To access the CPU module from either of the following modules or engineering tools, the size of the file register needs to be
5696K words or less with an extended SRAM cassette (NZ2MC-16MBS) of 16MB.
C Controller module
MES interface module
GOT2000 (when the programmable controller program monitor (R ladder) is used)
Engineering tool version 1.015R or earlier
CPU Module Logging Configuration Tool version 1.49B or earlier
GX LogViewer version 1.49B or earlier
MX Component version 4.10L or earlier
Item Description Setting range Default
Use Or Not Setting Specify whether or not file registers should be used. Not Use
Use File Register of Each Program
Use Common File Register in All Programs
Not Use
Capacity Specify the capacity of the file register in increments of 1K
words when "Use Common File Register in All Programs" is
selected.
This value depends on whether or not the
extended SRAM cassette is mounted and its
capacity. ( Page 96 The setting range of the
capacity of each area)
File name Assign a file name to the file register when "Use Common
File Register in All Programs" is selected.
1 to 60 characters