EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R-R04CPU - Module Access Device

Mitsubishi Electric MELSEC iQ-R-R04CPU
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21 DEVICES
21.6 Module Access Device
351
21
21.6 Module Access Device
This device directly accesses from the CPU module to the buffer memory of the intelligent function module mounted on the
main base unit and extension base unit.
Specify this device with 'Un\Gn'. (Example: U5\G11)
When reading/writing the buffer memory data using the module access device more than twice within a
program, the processing speed can be increased by conducting read/write operations at a single point of the
program using the FROM/TO instruction.
When data is written using more than one module access device:
When data is written at a single point of the program using the TO instruction:
(1) Store data to devices such as the data register (D).
(2) Write data to only one point in the program.
Specified item Value to be specified
Un Start I/O number of intelligent function modules Upper two digits when a start I/O number is described in three digits
(00H to FFH)
Example: 1F stands for X/Y1F0
Gn Buffer memory address 0 to 268435455 (decimal)
MOVP K0
MOVP K10
MOVP K5
MOVP K100
U0\
G10
U0\
G11
U0\
G12
U0\
G13
MOVP K0 D0
MOVP K10 D1
MOVP K5 D2
MOVP K100 D3
T0 H0 K10 D0 K4
(2)
(1)