638
37 FUNCTIONS
37.3 Memory Copy from Control System to Standby System
Files copied by the memory copy function
The following table lists the files to be copied by the memory copy function.
: Memory copy possible, : Memory copy not possible, : Storage not possible
When the memory copy is executed, files are copied after the memory of the standby system that has
differences is initialized. ( Page 641 Automatic memory initialization)
The memory copy cannot be executed to the files such as event history and those files are deleted from the
memory of the standby system CPU module. Back up the files before executing the memory copy as required.
When the security key authentication function is used
The security key of the CPU module is not copied to the standby system. Write the security key from the personal computer
where the security key is registered again after completion of the memory copy.
If the memory copy is executed when the security key is written in the CPU module, program files and their security keys are
copied but the security key of the CPU module is not copied. Starting up the CPU module without re-writing of the security key
causes an error of the CPU module because the security keys do not match between those program files and the CPU
module.
If the security key of the CPU module is written in an extended SRAM cassette, the replaced CPU module can
take over the security key by simply replacing the extended SRAM cassette at replacement of the CPU
module. In this case, re-writing of the security key after completion of the memory copy is not required.
File type Copy
CPU built-in memory SD memory card
Program memory Device/label
memory
Data memory
Standard program 
Standard FB file 
Standard CPU parameter 
System parameter 
Standard module parameter 
Module extension parameter 
Module-specific backup parameter 
Memory card parameter 
Device comment 
Device initial value 
Standard global label setting file 
Label initial value file Global label initial value file 
Local label initial value file 
File register 
Event history 
Device data storage file 
General-purpose data 
Remote password 
Safety program 
Safety FB file 
Safety CPU parameter 
Safety module parameter 
Safety global label setting file 
Standard/safety shared label setting file 