APPX
Appendix 1 Error Codes
759
A
3E00H Operation circuit
error
CPU module, SIL2 function
module, safety function module
An error has been detected in the
CPU module, SIL2 function
module, or safety function module.
Redundant function module
An error has been detected in the
redundant function module.
Stop CPU module, SIL2 function module,
safety function module
Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Redundant function module
Reset the CPU module.
If the error code is displayed again
even after taking an action, please
consult your local Mitsubishi
representative.
Failure
information
At power-on,
at RESET
3E01H Operation circuit
error
An error has been detected in the
CPU module, SIL2 function
module, or safety function module.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Failure
information
At END
instruction
execution, at
power-on, at
RESET
3E10H Circuit error An error has been detected in the
CPU module, SIL2 function
module, or safety function module.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Failure
information
At END
instruction
execution, at
power-on, at
RESET
3E11H
3E12H At power-on,
at RESET
3E20H Program
execution error
The entire program was executed
without executing the END
instruction.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Failure
information
At END
instruction
execution
3E22H Program
execution error
The FB/FUN program did not
com
plete successfully.
At instruction
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing