Appendix 1  Error Codes
■Error codes related to the online module change function
The following table lists the codes of errors related to the online module change function.
The code of an error detected during online module change is stored in SD1618 (Online module change error code).
The code of an error when a disable request is executed during online module change is stored in SD1619 (Disable request 
error code during online module change).
Error 
code
Error name Error details and cause Action
4110H Online module 
change error
The online module change function was executed while the 
CPU module was in a error state (stop error).
The module cannot be changed online. Power off the 
programmable controller, and replace the module.
4111H In a multiple CPU system, the online module change function 
was executed even though other CPU modules have not 
started up.
Execute the function again after all the CPU modules in the 
system start up.
4202H • An attempt was made to change two modules directly at the 
same time.
• A module that is not ready to be removed was removed.
• Continue processing for the module being changed online. 
Two modules cannot be changed online at the same time. 
For the other module, power off the programmable 
controller, and replace the module.
• Turn on SM1602 (Module removal request flag) and check 
that the value, 5, is stored in SD1617 (Online module 
change progress status). Then, continue processing from 
the step for mounting a module.
4205H The online module change function was executed in a multiple 
CPU system where a CPU module that does not support this 
function is included.
The module cannot be changed online. Power off the 
programmable controller, and replace the module.
4206H An attempt was made to change the inter-module 
synchronization target module online.
The module cannot be changed online. Power off the 
programmable controller, and replace the module.
4210H The selected module is out of the valid range. Check and correct the target base unit number and/or slot 
number, and turn on SM1600 (Module selection request flag) 
again.
4214H The model of the newly-mounted module differs from that of 
the module before online change. Or, the newly-mounted 
module is not upward compatible (module mismatch).
Mount the same model or the upward compatible module, and 
execute the request again.
• Mount a module of the same model, and perform the module 
recognition processing again.
4215H • The module recognition processing is performed without the 
module being mounted.
• The module selection processing is performed to the slot 
that is set as "Empty".
• The module newly-mounted to the system is not mounted 
correctly.
• Mount a module, and perform the module recognition 
processing again.
• Check and correct the target base unit number and/or slot 
number, and turn on SM1600 (Module selection request 
flag) again.
• Mount the module correctly.
4216H The module newly-mounted to the system online has failed. 
(The CPU module cannot access to the module.)
• The module has failed.
• The module is not mounted correctly.
Use another module, and execute the request again. Or, 
power off the system, and replace the module with the one that 
supports the online module change function.
• Replace the module with the normal one.
• Mount the module correctly.
4218H • The online change target module (before change) does not 
support the online module change function.
• The module newly-mounted to the system online (after 
change) does not support the online module change 
function.
• The online module change function was executed to change 
the MELSEC-Q series module.
• If an error occurs at the stage of selecting a module, the 
module cannot be changed online. Power off the 
programmable controller, and replace the module.
• If an error occurs at the stage of recognizing a module, 
replace the module with the one that supports the online 
module change function, and continue the processing.
• The module cannot be changed online. Power off the 
programmable controller, and replace the module.
421AH The online module change function was executed to change a 
module controlled by another CPU module.
Execute the function from the control CPU module.