5 TROUBLESHOOTING
5.6 List of Error Codes
129
5
11DH An incorrect UDP port specification has been received from the
external device.
Check whether the external device is set to use UDP port
number 2222 for EtherNet/IP communications.
Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
The external device may not be able to send data at the
specified RPI due to a high communication load, so specify a
larger RPI and connect again.
11EH Participation in a multicast group has failed. Take measures to reduce noise.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi
representative.
11FH An error was detected in the memory. Take measures to reduce noise.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi
representative.
120H The available resources are insufficient. Take measures to reduce noise.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi
representative.
121H The connection has stopped. The line may be busy, so retry at a later time.
The external device may not be able to send data at the
specified RPI due to a high communication load, so specify a
larger RPI and connect again.
126H An incorrect RegisterSession command has been received. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
128H An incorrect request frame has been received. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
129H An incorrect session handle has been received. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
12AH Request data with an incorrect size has been received. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
12BH Request data including an unsupported protocol version has
been received.
Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
12DH Request data with an incorrect size has been received. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
12EH Communications have been disconnected. Check whether 'EtherNet/IP communication start request' (Y10) is
on.
12FH The connections have been disconnected. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
130H to 131H Forward Close has been received from the external device. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.