162
APPX
Appendix 4 Details of Message Communication Support Command
Instance attribute (instance ID: 01H)
*1 The setting data is saved to non-volatile memory.
*2 The setting data is enabled the next time the module starts.
Details of interface status
Attribute
ID
Access
(: Available, :
Not available)
Name Data
type
Description Setting value
(Set)/stored
value (Get)
Get Set
1 Status DWORD Interface status Page 162
Details of
interface status
2 Configuration Capability DWORD Interface capability flag Page 163
Details of
interface
capability flag
3 Configuration Control DWORD Interface control flag Page 163
Details of
interface control
flag
4 Physical Link
Object
Path size UINT Path size of physical link object 0002H
Path Padded
EPATH
Logical segment that identifies the
physical link object
•0: 20H
•1: F6H
•2: 24H
•3: 01H
5 Interface
Configuration
IP Address UDINT IP address of the device Set values of
parameters
Network Mask UDINT Network mask of the device
Gateway Address UDINT Default gateway address
Name Server UDINT Primary name server 00000000H
Name Server 2 UDINT Secondary name server 00000000H
Domain Name STRING Default domain name " " (null
character)
6 Host Name STRING Host name " " (null
character)
8 
*1*2
TTL Value USINT TTL value for EtherNet/IP multicast
packets
1 to 255
9 
*1*2
MCast Config Alloc Control USINT IP multicast address setting Page 163
IP multicast
address setting
value
Reserved USINT Reserved 00H
Num Mcast UINT Number of IP multicast addresses to
assign for EtherNet/IP
1 to 32
Mcast Start Addr UDINT First multicast address from which to start
assignment
Value on the left
13 
*1
Encapsulation Inactivity Timeout UINT Sets the time until the TCP connection or
DTLS session is closed
(unit: seconds)
1 to 3600
0 is invalid.
(Default: 120)
Bit Description Value
0 to 3 Interface Configuration Status Fixed to 2 (to set the IP address acquired from the parameter settings)
4 Mcast Pending 0: No changes to TTL Value and Mcast Config
1: In the wait-for-restart state due to changes to TTL Value and Mcast Config

Table of Contents