1 FUNCTIONS
1.17 Redundant System Function
225
1
Communication path bypass function
When a communication error occurs between the application and Ethernet-equipped module supporting the following
redundant system, the path on which the error occurs is bypassed so that communication can continue without changing the
communication path setting.
• Applications operating on OPS
•GX Works3
The communications path bypass function cannot be used for direct connection. Use for connection via a hub.
Setting procedure
The bypass function is always enabled. The parameter setting is not required.
Precautions
If an Ethernet-equipped module detects a disconnection or communication error, it does not release the relevant connection
until the alive check function detects an error.
When a disconnection or communication error occurs continually, if the relevant connection has not been released, an
Ethernet-equipped module bypasses the communication path by using a new connection.
For that reason, if a disconnection or communication error is detected over and over again in a short period of time, available
connections run out and an error occurs in GX Works3.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric MELSEC iQ-RJ71EN71 and is the answer not in the manual?

Mitsubishi Electric MELSEC iQ-RJ71EN71 Specifications

General IconGeneral
BrandMitsubishi Electric
ModelMELSEC iQ-RJ71EN71
CategoryController
LanguageEnglish

Related product manuals