132
2 PARAMETER SETTINGS
2.3 Basic Settings
Equal assignment and identical point assignment of link points
Equal assignment and identical point assignment can be set as follows.
[CC IE Field Configuration] [Equal Assignment] or [Identical Point Assignment]
Item Description Setting range
Equal Assignment Specify the start station and end station, and equally assign link devices to
stations.
Start Station: Enter the start station number of stations for which link
devices are equally assigned.
End Station: Enter the end station number of stations for which link
devices are equally assigned.
Start No.: Enter the start number of link devices to be equally assigned.
Total Points Assigned: Enter the total points of link devices to be equally
assigned.
Start Station: 0 to the end station number
End Station: Number set to "Start Station" to the
end station number
Start No.: Same values set in "RX/RY Setting"
and "RWw/RWr Setting"
Total Points Assigned: Same values set in "RX/
RY Setting" and "RWw/RWr Setting"
(Default: Blank)
Identical Point
Assignment
Assign the same link device points to all stations.
Points entered in this field will be reflected to the "Points" of "RX/RY
Setting".
Half of the points entered in this field will be reflected to the "Points" of
"RWw/RWr Setting".