3 PROGRAMMING
3.3 Communication Example of Safety Communication Function
179
3
12. Set the network configuration as follows.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Basic Settings] [Network
Configuration Settings]
RX/RY and RWw/RWr setting of the local station is for standard communications.
RX/RY setting of the remote device station is used as a remote control and monitor input signal in standard
communications.
RWw/RWr setting of the remote device station is used in the system of safety communications. Always set 16 points.
13. Set the refresh settings as follows.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Basic Settings] [Refresh Settings]
The refresh settings are for standard communications.
14. Log on to the programmable controller.
[Online] [User Authentication] [Log on to PLC]
If logon cannot be performed, writing user information or initializing all information of the programmable controller is
required. ( GX Works3 Operating Manual)
15. Write the set parameters to the Safety CPU on the master station.
[Online] [Write to PLC]