3 PROGRAMMING
3.3 Communication Example of Safety Communication Function
16. Set the parameters of the remote device station in the "CC IE Field Configuration" window as shown below and write the
parameters.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Basic Settings] [Network
Configuration Settings] Select the NZ2GFSS2-32D in the list of stations. [CC IE Field Configuration] [Online]
[Parameter Processing of Slave Station]
• For items other than above, write the initial value.
• Select [Close with Reflecting the Setting] and close the "CC IE Field Configuration" window after writing parameters of the
remote device station.
17. Visually check if the parameter of the remote device station is correctly written after writing parameters. For how to check
the parameters, refer to the following.
GX Works3 Operating Manual
18. Set "To Use or Not to Use the Safety Communication Setting" to "Use".
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Application Settings] [Safety
Communication Setting] [To Use or Not to Use the Safety Communication Setting]
19. Select "Local Network" from "Communication Destination" in "Safety Communication Setting" window and set the
destination module in "Select the target module for the Safety Communication Setting" window.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Application Settings] [Safety
Communication Setting] [Safety Communication Setting]
20. Set the safety communication setting as follows.
Name Write value
Wiring selection of input X0 1: Double wiring (NC/NC)
Wiring selection of input X1 1: Double wiring (NC/NC)
Ext. module 1_Wiring selection of
output Y0
1: Double wiring (Source/Source)
Ext. module 1_Wiring selection of
output Y1
1: Double wiring (Source/Source)