272
4 TROUBLESHOOTING
4.5 List of Error Codes
D615H Parameter error (each station device range
assignment error (RY))
Write the network parameter to the CPU module
again.
Execute again after correcting the size of the slave
station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D616H Parameter error (each station device range
assignment error (RY))
Write the network parameter to the CPU module
again.
Execute again after correcting the offset of the slave
station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D617H Parameter error (each station device range
assignment error (RX))
Write the network parameter to the CPU module
again.
Execute again after correcting the size of the slave
station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D618H Parameter error (each station device range
assignment error (RX))
Write the network parameter to the CPU module
again.
Execute again after correcting the offset of the slave
station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D619H Parameter error Write the network parameter to the CPU module
again.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61AH Parameter error Write the network parameter to the CPU module
again.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61BH Parameter error (device overlap error (RWw)) Write the network parameter to the CPU module
again.
Execute again after correcting the offset or size of
the slave station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61CH Parameter error (device overlap error (RWr)) Write the network parameter to the CPU module
again.
Execute again after correcting the offset or size of
the slave station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61DH Parameter error (device overlap error (RY)) Write the network parameter to the CPU module
again.
Execute again after correcting the offset or size of
the slave station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61EH Parameter error (device overlap error (RX)) Write the network parameter to the CPU module
again.
Execute again after correcting the offset or size of
the slave station link device in the setting data.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61FH Parameter setting by the CCPASET instruction has
failed.
Execute again after setting "Setting Method of Basic/
Application Settings" under "Parameter Setting
Method" in "Required Settings" to "Program".
D620H The transient data is incorrect. Correct the transient data at the request source,
and retry the operation.
If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
Error
code
Error details and causes Action Detailed Information