5. PARAMETERS
5 - 9
Control
mode
No./symbol/name
Setting
digit
Function
Initial
value
[unit]
PST
PA02
REG
Regenerative
option
_ _ x x Regenerative option selection
Used to select the regenerative option.
Incorrect setting may cause the regenerative option to burn.
If a selected regenerative option is not for use with the servo amplifier, [AL. 37
Parameter error] occurs.
00: Regenerative option is not used
For servo amplifier of 100 W, regenerative resistor is not used.
For servo amplifier of 0.2 kW to 7 kW, built-in regenerative resistor is used.
01: FR-RC/FR-CV/FR-BU2
When you use FR-RC, FR-CV, or FR-BU2, select "Mode 2 (_ _ _ 1)" of
"Undervoltage alarm detection mode selection" in [Pr. PC27].
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50 (Cooling fan is required.)
08: MR-RB31
09: MR-RB51 (Cooling fan is required.)
0B: MR-RB3N
0C: MR-RB5N (Cooling fan is required.)
00h
_ x _ _ For manufacturer setting 0h
x _ _ _ 0h
PA03
ABS
Absolute
position
detection
system
_ _ _ x Absolute position detection system selection
Set this parameter when using the absolute position detection system in the
position control mode.
0: Disabled (incremental system)
1: Enabled (absolute position detection system by DIO)
0h
_ _ x _ For manufacturer setting 0h
_ x _ _ 0h
x _ _ _ 0h
PA04 _ _ _ x For manufacturer setting 0h
AOP1
_ _ x _ 0h
Function
selection A-1
_ x _ _ 0h
x _ _ _ Forced stop deceleration function selection
0: Forced stop deceleration function disabled (EM1)
2: Forced stop deceleration function enabled (EM2)
Refer to table 5.1 for details.
2h
Table 5.1 Deceleration method
Deceleration method
Setting
value
EM2/EM1
EM2 or EM1 is off Alarm occurred
0 _ _ _ EM1 MBR (Electromagnetic
brake interlock) turns off
without the forced stop
deceleration.
MBR (Electromagnetic
brake interlock) turns off
without the forced stop
deceleration.
2 _ _ _ EM2 MBR (Electromagnetic
brake interlock) turns off
after the forced stop
deceleration.
MBR (Electromagnetic
brake interlock) turns off
after the forced stop
deceleration.
PA05
FBP
Number of
command input
pulses per
revolution
The servo motor rotates based on set command input pulses.
To enable the parameter value, select "Number of command input pulses per
revolution (1 _ _ _)" of "Electronic gear selection" in [Pr. PA21].
Setting range: 1000 to 1000000
10000