Appendix 3 List of Special Register Areas
D9095 SD1095 SD200
DIP switch
information
DIP switch
information
This register stores a status of the DIP switch of the CPU
module in the following format.
• 0: OFF
• 1: ON
Qn(H)
QnPH
D9100 SD1100
Fuse blown
module
Bit pattern in units
of 16 points,
indicating the
modules whose
fuses have blown
• The number of an output module whose fuse has blown
is stored in the following bit pattern (in units of 16 points).
(If the module numbers are set by parameter, the
parameter-set numbers are stored.)
For a module whose number of output points exceeds 16
points, all bits corresponding to output module numbers
within the number of output points occupied by the module
(in increments of 16 points) turn on.
Example: When a 64-point module is mounted on the slot 0,
b0 to b3 turn on when the fuse has blown.
• Output modules on remote I/O stations are also checked
for blown fuse. (This register must be cleared by a
program because the bit status remains unchanged even
after clearing the error.)
Qn(H)
QnPH
QnU
*1
LCPU
*2
D9101 SD1101
D9102 SD1102
D9103 SD1103
D9104 SD1104
D9105 SD1105
D9106 SD1106
D9107 SD1107
D9108 SD1108
Step
transfer
monitoring
timer setting
Timer setting valve
and the F number
at time out
• This register stores a value set for step transition
monitoring timer and the number of an annunciator (F
number) that turns on if the monitoring timer times out.
• Turning on any of registers SM1108 to SM1114 activates
a monitoring timer. If the transition condition for the step
is not established before the time-out time, the
annunciator (F) turns on.
Qn(H)
QnPH
D9109 SD1109
D9110 SD1110
D9111 SD1111
D9112 SD1112
D9113 SD1113
D9114 SD1114
ACPU
special
register
Special
register
after
conversion
Special
register
after
modification
Name Meaning Explanation
Corresponding
CPU
SW1
SW2
b0b1b2b3b4b5b15
SW3
SW4
SW5
D9095
0
to
b15 b14b13b12b11b10
b9
b8
b7 b6 b5 b4 b3 b2 b1 b0
00000000
1
(Y80)
000
1
(YC0)
000
0000000000000000
00000000000000
1
Y7
B0
1
Y7
30
SD1100
SD1101
SD1107
Indicates a fuse blown state.
b15 b7 b0b8to to
(02 to 255)
F number setting Timer time limit setting
(1 to 255s (1s units))